CASA G / WATER REUSE · WORKING COORDINATION STUDY
Rain to the garden.
Rain to the toilets.
The E15 cistern is restored west of the house. Four main-roof scuppers and straight downpipes feed two shared buried collectors, an accessible filter and a separate rainwater tank.
Open the model ↗ · Rainwater IFC aligned with the house · Calculation and source data
RESTORED STORAGE
5,000 L
Usable volume · 6,500 L gross interior allowance. Product and structural design pending.
COLLECTABLE IN A REFERENCE YEAR
LOCAL RAINFALL REFERENCE
926 mm/year
Municipal climate strategy, 1976–2005 historical reference. Monthly estimates use a scaled Coimbra/Bencanta seasonal profile.
Storage cannot create summer rainfall. The 5 m³ option preserves the previous design and provides a starting allowance; it is not an established economic optimum or a promise of summer autonomy. Toilet backup and irrigation curtailment are necessary provisions.
When water arrives and when it is needed
Blue: captured water. Ochre: demand. Monthly estimates, m³.
What was recovered, and what changed
Only the main roof is counted. The rejected perimeter canopy pipes have been removed, so canopy runoff is excluded from the yield estimate. Lower accessible terraces, balconies and retaining-wall drains are also excluded. Four source scuppers connect to straight downpipes; the south pair sits 110 mm farther out than the previous top section to clear the balcony beam without a mid-height bend. Short connections remain at roof outlets and buried collectors.
The old 6.08 m³ retention volume is kept as a separate overflow reservation. Infiltration and the final outfall remain unconfirmed. No rainwater route connects to the domestic sewage pumping station.
Calculation basis
Green-roof monthly runoff is not measured: 0.40 is an explicit screening assumption, not an ANQIP monthly coefficient. Use a daily local rain series and the selected roof system’s measured response before fixing the tank size. The 30% drier scenario is a sensitivity test, not a return-period drought.
A monthly net balance repeats the reference year until initial and final storage agree. Storage = previous storage + collection − delivered demand − overflow. No free full tank is added each January. Tank options are compared using the same inflow and demand.
System provisions to detail
Provide a covered, inspectable tank, inlet filtration, controlled first-flush diversion, calming inlet, floating draw-off and a screened vent. The non-potable delivery network needs a pump/controller, separate marking and protected backup through an appropriate air gap. Confirm water quality for toilet use, including potential green-roof colour and dissolved contaminants.
These are provisions for the next design stage: pressurised supply pipes to the toilets and garden, pump head, treatment, vent termination and bypass disposal are not yet modelled. Storm intensity must separately size gutters, outlets, filters, collectors, independent emergency roof drainage and overflow. Tank wall design, buoyancy and excavation are also unresolved.
ANQIP ETA 0701 is technical guidance, not a law. Its sections 4.1–4.5 address collection/storage and 4.6–4.8 address use, water quality and backup. It recommends gross volume at least 20% above usable volume. This model reserves 30%. No compliance certification is claimed.